Published at : 07 Dec 2023
Volume : IJtech
Vol 14, No 7 (2023)
DOI : https://doi.org/10.14716/ijtech.v14i7.6665
Rossy Armyn Machfudiyanto | Department of Civil and Environmental Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok 16424, Indonesia |
Leni Sagita Riantini | Department of Civil and Environmental Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok 16424, Indonesia |
Titi Sari Nurul Rachmawati | Department of Architectural Engineering, Kyung Hee University, Yongin-si 17104, Korea |
Ayomi Dita Rarasati | Department of Civil and Environmental Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok 16424, Indonesia |
Mochamad Daffa Alfiansyah Rachman | Department of Civil and Environmental Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok 16424, Indonesia |
Wasteful consumption of electricity in
high-rise building in Indonesia is the primary trigger for the increase in
carbon emissions. Predominantly, the excessive use of electrical appliances and
air conditioning systems is the principal factor contributing to the use of
energy within these structures. To effectively address this issue, the
importance lies in adopting suitable building envelope material. Therefore,
this study aimed to analyze the effectiveness of different insulation types and
roof covering in improving the energy-saving performance of office building.
There were six proposed renovation for the flat roof of building, consisting of
two approaches, namely (1) the incorporation of insulation and (2) the
replacement of roof covering layers. Scenarios A1, A2, and A3 have incorporated
100 mm of polyurethane (PU) foam, polyisocyanurate (PI) foam, and fiberglass
batt into the design. Meanwhile, Scenarios B1, B2, and B3 opted for ceramic
material, Ethylene Propylene Diene Terpolymer (EPDM) membrane, and grass vegetation
as roofing material for the existing roof. The results showed that the addition
of insulation to roof through Insight 360 and the replacement of roof covering
layers produced an energy reduction of 19.5% to 20.2% and 19.5% and 23.5%,
respectively. The implementation of green roof in scenario B3 was selected as
the most promising renovation option, achieving a remarkable 23.5% reduction in
energy consumption.
Covering Layers; Energy Usage; Flat Roof; Insulation Layers
High-rise
building in Indonesia is contributing to an increase in carbon gas emissions.
The increase in carbon gas emissions is caused by the extensive operations of
conventional power plants, required to meet the high electricity demands of building.
Among the various types of high-rise building, office is object with the
highest energy consumption. In 2020, Energy Use Intensity (EUI) of 213.27
kWh/m2/year was produced (B2TKE-BPPT, 2020).
The major factor behind the electricity demand is the excessive use of air
conditioning to maintain indoor thermal comfort, regardless of the weather (Hakim et al., 2021). Therefore, providing
warm and cool rooms during rainy and dry seasons can reduce excessive reliance
on air conditioning and energy use.
The presence of a fit building envelope can prevent rapid heat
transfer, effectively regulating indoor thermal comfort. Building envelope
includes the outermost layer of architectural elements, namely
walls, roof, basement, doors, windows, and other external element that
withstands the surrounding environment (Bachrun, Ming, and Cinthya, 2019). Roof is one of the most essential envelope
components for maintaining the quality of indoor thermal comfort and reducing
the energy consumption of building. The study by (Feng et al., 2020) showed that the installation of insulation material on roof
reduced energy consumption by up to 78%. Furthermore, (Ibrahim et al., 2018) proved that a roof design with
ventilation effectively mitigated overheating. Building designers commonly use
various roof insulation material, including polyurethane (PU) foam,
polyisocyanurate (PI) foam, and fiberglass batts. Even with the comparable attributes,
PU foam is distinguished by its low thermal conductivity and density (Gama, Ferreira, and Timmons, 2018), while PI shows reduced thermal conductivity
under low-temperature conditions (Makaveckas,
Bliudzius, and Burlingis, 2021). Meanwhile, fiberglass batts are good in insulation performance
due to the higher R-value.
The type of
covering material used for roof affects its ability to absorb or reflect heat.
The study by (Algarni, Almutairi, and Alqahtani, 2022) showed that green roof with
shallow-rooted grass lowered energy usage by 3.6% in six months (Shaharuddin, Khalil, and Saleh, 2019). Apart from the use of green roof, ceramic tiles and Ethylene
Propylene Diene Terpolymer (EPDM) membranes can also serve as roofing material.
(Sedaghat et al., 2023) showed that these tiles were capable of reflecting solar radiation
by up to 50%, resulting in energy savings for building. EPDM membranes also
show commendable reflective qualities, particularly when white in color.
Therefore, the incorporation of suitable insulation material and roof covering
can help anticipate an increase in electricity consumption due to rapid heat
transfer.
Insulating
and using covering material must be adapted to the geometric shape of an office
building. In this context, flat roof represents the most prevalent geometric
configuration found in office building, satisfying the functional requirements
of HVAC system components. Prior study substantiated the effectiveness of using
insulation and covering material on flat roof. The comparison between roof
insulation usage and the addition of covering layers has not been addressed.
Therefore, this study aims to analyze the effectiveness of different insulation
types and roof covering in improving the energy-saving performance of office
building. Building designers should be assisted in selecting the most effective
flat roof renovation options to minimize energy usage.
In this section, a description of the study process is provided
and the flow of each stage is shown in Figure 1. This study used
a design model in which the dimensions and location of the selected design were
determined based on the latest government data on building energy consumption
Figure 1 Study methods workflow
Table 1 Summary of material types
and thickness for initial design
Envelope
Component |
Material
selection |
Thickness |
Basement
Exterior Wall |
Concrete,
Cast-in-place |
150 mm |
Sand/cement
screed |
20 mm | |
Exterior
Insulation |
100 mm | |
Plaster |
12.5 mm | |
Façade Wall |
Concrete,
Precast |
100 mm |
Sand/cement
screed |
20 mm | |
Rigid
insulation |
50 mm | |
Gypsum
wallboard |
12 mm | |
Plaster |
12.5 mm | |
Curtain Wall |
Aluminium
frame |
50 mm |
|
Triple
glazing Low-e glass |
30 mm |
Table 1 Summary of material and
thickness for initial design [Cont.]
Envelope Component |
Material
selection |
Thickness |
Floors |
Concrete,
Cast-in-place |
100 mm |
Sand/cement
screed |
20 mm | |
Plaster |
12 mm | |
Carpet tile |
10 mm | |
Ceiling |
Metal stud
layer |
45 mm |
Rigid
insulation |
50 mm | |
Gypsum
wallboard |
12 mm | |
Roof |
Concrete, Cast-in-place |
150 mm |
Sand/cement
screed |
50 mm | |
Vapor
retarder |
membrane | |
Roofing felt |
4 mm |
The initial
building design was created using Autodesk Revit and default settings. The
default settings are inherently consistent with ASHRAE standards, obviating the
necessity for system adjustments, as explained in Table 2. Following the
completion of the initial building design, the initial EUI analysis was
conducted using Insight 360. The energy analysis used an equation created based
on the DOE 2.2 engine program, where the initial EUI calculations were compared
to the six renovation scenarios.
Table 2 Summary of space type distribution for each
room
Room name |
Space type |
Criteria |
Lobby |
Lobby -
Office |
6 Am to 11 PM
operating schedule |
Heating set
point: 21.11oC | ||
Cooling set
point: 23.89oC | ||
Lighting
load: 13.99 W/m2 | ||
Power load:
5.81 W/m2 | ||
Canteen;
Meeting room |
Office
Enclosed; Dining Area |
6 Am to 11 PM
operating schedule |
Heating set
point: 21.11oC | ||
Cooling set
point: 23.89oC | ||
Lighting
load: 10 W/m2 | ||
Power load:
5.81 W/m2 | ||
Praying room |
Religious
Building |
Retail
lighting operating schedule |
Heating set
point: 21.11oC | ||
Cooling set
point: 23.89oC | ||
Lighting
load: 13.99 W/m2 | ||
Power load:
5.81 W/m2 | ||
Working area |
Office - Open
plan |
6 Am to 11 PM
operating schedule |
Heating set
point: 21.11oC | ||
Cooling set
point: 23.89oC | ||
Lighting
load: 11.84 W/m2 | ||
Power load:
16.15 W/m2 | ||
Toilet |
Dressing/Locker/Fitting
room |
6 Am to 11 PM
operating schedule |
Heating set
point: 21.11oC | ||
Cooling set
point: 23.89oC | ||
Lighting
load: 6.03 W/m2 | ||
Power load:
5.81 W/m2 |
The two categories of renovation implemented in this study are 1) the incorporation of 100 mm-thick roof insulation and 2) the
adoption of novel roofing material. The first type of renovation introduced PU
foam, PI foam, and fiberglass batt materials onto roof, denoted as Scenarios
A1, A2, and A3, respectively. The selection of these three materials was
informed by the existence of prior studies discussing the characteristics, as
shown in the Introduction section. Furthermore, the second renovation category
comprised the use of glossy ceramic, EPDM membrane, and vegetation layers,
identified as Scenarios B1, B2, and B3. The vegetation layer included a
waterproof to prevent seepage into the concrete, soil serving as a growth
medium, and a layer of grass and rocks as the topmost cover. These three
roofing materials were selected for the capacity to create a cool roof environment by reflecting or
absorbing sunlight, which cools the space beneath. Finally, the most preferable renovation scenario for diminishing EUI
value is shown in the conclusion.
This section shows the outcomes derived from the calculations conducted through Insight 360. Subsequently, a comprehensive discussion will be provided, delving into the comparative analysis among the various scenarios. Building design model is shown in Figure 2, where the colors do not influence the energy analysis results. In Figure 2, the basement and roof floors are black and gray, respectively.
Figure 2 Building design model using Autodesk Revit:
basement (black) and roof (gray)
Energy analysis conducted using Insight 360
showed that the initial EUI value for the designed building was 272 kWh/m2/year.
According to the government data
Table 3 EUI calculation results for each
renovation scenario
Scenario id |
Criteria |
Initial EUI
value (kWh/m2/year) |
Final EUI
value (kWh/m2/year) |
% Reduction |
A1 |
Insulating PU
foam |
272 |
219 |
19.49 |
A2 |
Insulating PI
foam |
272 |
217 |
20.22 |
A3 |
Insulating
fiberglass batt |
272 |
217 |
20.22 |
B1 |
Using glossy
ceramic |
272 |
219 |
19.49 |
B2 |
Using EPDM membrane |
272 |
218 |
19.85 |
B3 |
Implementing
green roof |
272 |
208 |
23.53 |
Previous
studies showed that EUI calculation was influenced by the heat transfer
capability of building envelope material. The capability can be measured using
thermal coefficient commonly referred to as U-value (W/m2. K). Based
on the basic formula, U-value is affected by thermal conductivity () and
material thickness. Table 4 presents values of each material used in
Scenarios A and B, with the corresponding U-value and roof thicknesses after
the renovation. Roof thickness in Scenario A remains consistent using the same
insulation thickness, specifically 100 mm. Meanwhile, Scenario B shows
variations in roof thickness due to adjustments made to accommodate the
dimensions of each type of roof covering.
Table 4 Summary of U-value for each material used
(W/m.K) |
Thickness (mm) |
U-value (W/m2.K) | |
PU foam |
0.032 |
204 |
0.2955 |
PI foam |
0.02 |
204 |
0.1902 |
Fiberglass |
0.019 |
204 |
0.1811 |
Glossy ceramic |
0.84 |
238 |
3.748 |
EPDM membrane |
0.138 |
278 |
1.6202 |
Green roof |
- |
251 |
0.4694 |
As presented in Table 4, Scenario A reported lower U-value compared to Scenario B. U-value increases with higher , even though Scenario A had the same roof thickness. The results were consistent with the theory that an increase in U-value was directly proportional to but inversely related to material thickness. Despite a lower value and thicker layer compared to green roof, the calculation showed that green roof U-value was lower than EPDM membrane. This contradicts existing theories, suggesting the presence of other factors influencing U-value of material.
The drainage and substrate layers act as heat
absorbers while simultaneously providing a cooling effect on roof area of
building. This phenomenon occurs because the substrate and drainage layers
consist of organic material with high emissivity values, facilitating an
extremely efficient heat transfer circulation. According to (Yildirim, Ozburak, and Ozden, 2023) and (Wang , Huang, and Li, 2021), green roof
possesses the capability to provide a cooling effect on building roof through
effective heat transfer circulation. A reduction in U-value becomes possible
through this mechanism and green roof was intentionally designed with densely
packed grass vegetation. This was conducted to ensure that incoming heat could
be effectively absorbed by the high grass density, reducing heat convection
into building. The observation is consistent with
The examination of the relationship between U-value and EUI shows interesting trends. Scenario A, comprising A1, A2, and A3, shows that smaller U-value corresponds to lower EUI value, particularly evident with fiberglass batts. However, Scenarios B1 and B2 reports EUI value that can match or be lower than A1, despite having U-value five times higher. This contradicts the results of (Carvalho et al., 2021), where smaller U-value leads to lower EUI value. This phenomenon is attributed to the low emissivity values of glossy ceramic and EPDM membranes in B1 and B2, which effectively block excessive solar heat radiation, showing a reflective effect. This study also explores the influence of thermal conductivity and thickness on EUI, as presented in Figure 3. A linear relationship was observed between higher thermal conductivity and larger EUI value, as well as a negative correlation with thickness. However, the very low R2 value is due to the lack of data samples, resulting in a non-normal distribution. The need for additional data samples becomes apparent to ensure and strengthen the statistical validity of the results. However, the trendline shows a relationship consistent with the results in this study.
Figure 3 The trendline of thermal conductivity and
thickness with EUI value
The
results complement previous studies on energy assessment in
building roof renovation, as shown in Table 5 with five previous examples. The
study by (Borras et
al., 2022) reported the
installation of three types of building roof renovation including 2 green roofs
in 6 different climate zones in Spain. Therefore, a more comprehensive change
in building envelope led to a higher reduction in EUI. According to (He
et al., 2020), cool roof was
more effective in reducing a building's EUI due to the excellent reflectivity
compared to green roof. However, (Jovanovic
, Zivkovic, and Stevanovic, 2018) stated the advantages of
green roof in improving indoor and outdoor building quality by generating
additional oxygen and absorbing air pollutants. (Cai et al., 2019) also provided evidence that
green roof was effective in reducing EUI and room temperature.
Table 5 Five examples of previous study outcomes
No |
Previous
study title |
Study outcomes |
1 |
Contribution
of green roof to energy savings in building renovation (Borras
et al., 2022) |
Among the
three types of roof renovation, showed a decrease in energy consumption by 9%
to 13% |
2 |
Thermal and
energy performance of green roof and cool roof: A comparison study in
Shanghai area (He et al., 2020) |
Cool roof was
superior in reducing room temperature, resulted in more significant
electricity savings compared to green roof |
3 |
Inverted roof
insulation kits and their durability (Francke and Gerylo, 2018) |
The decrease
in the quality of insulation material was caused by freeze-thaw cycles. |
4 |
The impact of
building envelope with the green living system on the built environment (Jovanovic , Zivkovic, and Stevanovic, 2018) |
The
utilization of green roof and vertical gardens on facades reduced air
pollutant levels by up to 11 g/m2/year, eliminated air bacteria,
and contributed to building energy savings. |
5 |
Reduction in
Carbon Dioxide Emission and Energy Savings Obtained by Using Green Roof (Cai et al., 2019) |
The use of
green roof reduced energy consumption by up to 11.53 kWh/m2/year
while effectively preserving heat. |
From
Table 5, this study complements information regarding building energy analysis
concerning the addition of insulation and replacement of covering layers in
building roof renovation in a single discourse. This study also developed six
different scenarios including three types of insulation material and covering
layers. The energy calculation results showed that the use of green roof in
Scenario B3 obtained the highest percentage reduction in EUI. Meanwhile, the
addition of insulation in Scenarios A1-A3 did not have a significant impact on
reducing EUI despite the better heat transfer capability. Furthermore, the study conducted by (Francke and Gerylo, 2018) reported the limitations of insulation
material quality in response to environmental temperature changes. Based on EUI
calculation, the use of green roof is selected as the best solution for
application in office building roof in Jakarta.
In conclusion, the optimization of flat roof
was reported to prevent excessive building energy consumption. The
implementation of several envelope renovation showed that the addition of
insulation or alterations to roof covering effectively reduced EUI value. The
additional insulation layer restricted the solar heat radiation rate due to
extremely low conductivity, acting as a heat-absorbing material. Covering
material had a cooling effect on roof area. Through Insight 360 analysis, six
scenarios were investigated, resulting in energy consumption reductions ranging
from 19.49% to 20.22% for scenarios A1–A3. Similarly, Scenarios B1, B2, and B3
reduced energy consumption by approximately 19.49%, 19.5%, and 23.53%,
respectively. The final energy analysis and previous results showed that green
roof system in Scenario B3 yielded the most significant energy savings.
However, this study necessitated the incorporation of additional data regarding
insulation thickness and the varieties of covering material. This inclusion
aimed to enhance the data distribution efficacy, obtaining more accurate
results.
This study was funded by the Directorate of
Research and Development, Universitas Indonesia, under Hibah PUTI Q2 (Grant No.
NKB-821/UN2.RST/HKP.05.00/2023).
Algarni, S.,
Almutairi, K., Alqahtani, T., 2022. Investigating the Performance of Energy
Management in Office Buildings by Using a Suitable Green
Roof Design to Reduce the Building's Energy
Consumption. Sustainable Energy Technologies and Assessments, Volume
54(102825), pp. 1–8
Arabi, R., 2018. Assessment of Vegetation Cooling Effect
Through the Application of Green Roofs in Tropical
Campus Environment. Environmental Science. Available online at:
http://psasir.upm.edu.my/id/eprint/76306, Accessed on September 19, 2023
B2TKE-BPPT, 2020. Benchmarking Specific Energy Consumption in Commercial Building,
Serpong: Indonesian Government. Available online at: https://simebtke.esdm.go.id/sinergi/assets/content/20210527150029_Laporan_Akhir_SEC-130120.pdf,
Accessed on July 2, 2023
Bachrun, A.S., Ming, T.Z., Cinthya, A., 2019. Building Envelope
Component to Control Thermal Indoor Environment in Sustainable
Building: A Review. Sinergi, Volume 23(2), pp. 79–98
Berawi, M.A., Sari, M., Salsabila, A.A., Susantono, B.,
Woodhead, R., 2022. Utilizing Building Information Modelling in the Tax
Assessment Process of Apartments Buildings. International Journal
of Technology, Volume 13(7), pp. 1515–1526
Borras, J.G., Lerma, C., Mas, A., Vercher, J., Gil, E., 2022.
Contribution of Green Roofs to Energy Savings in Building Renovations.
Energy for Sustainable Development, Volume 71, pp. 212–221
Cai, L., Feng, X-P., Yu, J-Y., Xiang, Q-C., Chen, R., 2019. Reduction
in Carbon Dioxide Emission and Energy Savings Obtained by Using Green Roof.
Aerosol and Air Quality Research, Volume 19, pp. 2432–2445
Carvalho, J.P., Almeida, M., Braganca, L., Mateus, R., 2021.
BIM-based Energy Analysis and Sustainability
Assessment-Application to Portuguese Buildings. Buildings, Volume
11(246), pp. 1–25
Feng, H., Liyanage, D.R., Karunathilake, H., Sadiq, R., Hewage, K., 2020. BIM-based
life Cycle Environmental Performance Assessment of Single-Family Houses:
Renovation and Reconstruction Strategies for Aging Building Stock in
British Columbia. Journal of Cleaner Production, Volume 250(119543), pp.
1–17
Fitriani, H., Rifki, M., Foralisa, M., Muhtarom, A., 2022.
Investigation of Energy Saving Using Building Information Modeling for Building
Energy Performance In Office Building. Civil Engineering and Architecture,
Volume 10(4), pp. 1280–1292
Francke, B., Gerylo, R., 2018. Inverted Roof Insulation Kits
And Their Durability. Warsaw, MATEC Web of Conference. Available online at:
https://doi.org/10.1051/matecconf/201816308005, Accessed on September 6, 2023
Gama, N.V., Ferreira, A., Timmons, A.B., 2018. Polyurethane
Foams: Past, Present, and Future. Materials, Volume 11(10), pp. 1–35
Hakim, F.N., Muhamadinah, Y., Atthaillah, ., Mangkuto, R.A.,
Sudarsono, A.S., 2021. Building Envelope Design Optimization of a Hypothetical
Classroom Considering Energy Consumption, Daylighting, and Thermal
Comfort: Case Study In Lhokseumawe, Indonesia. International Journal of
Technology, Volume 12(6), pp. 1217–1227
He, Y., Yu, H., Ozaki , A., Dong, N., 2020. Thermal and
Energy Performance of Green Roof and Cool Roof: A Comparison
Study in Shanghai Area. Journal of Cleaner Production,
Volume 267(122205), pp. 1–15
Ibrahim, S.H., Roslan, Q., Affandi, R., Razali, A.W., Samat,
Y.S., Nawi, M.N.M., 2018. Study on the Optimum Roof Type with 30° Roof Angle to
Enhance Natural Ventilation and Air Circulation of a Passive Design. International
Journal of Technology, Volume 9(8), pp. 1692–1701
Jovanovic , D., Zivkovic, P., Stevanovic, Z., 2018. The Impact
of the Building Envelope with the Green Living System on
the Built Environment. Thermal Science, Volume 22, pp. 1033–1045
Makaveckas, T., Bliudzius, R., Burlingis, A., 2021.
Determination of the Impact of Environmental Temperature
on the Thermal Conductivity of Polyisocyanurate (PIR)
Foam Products. Journal of Building Engineering, Volume 41(102447), pp.
1–14
Sedaghat, A., Salem, H., Hussam, W.K., Mahdizadeh, A., Al-Khiami, M.I., Malayer, M.A., Soleimani, S.M., Sabati, M., Narayanan, R., Rasul, M., Khan,
M.M.K., 2023. Exploring Energy-Efficient Building Solution in Hot Regions: A
Study on Bio-Phase Change Material and Cool Roof
Coatings. Journal of Building Engineering, Volume 76(107258), pp. 1–22
Shaharuddin, S., Khalil, N., Saleh, A. A., 2019. Review of Significant
Maintenance Criteria for Tropical Green Roofs in Malaysia. International
Journal of Technology, Volume 10(1), pp. 69–80
Wang , L., Huang, M., Li, D., 2021. Strong Influence of Covective Heat
Transfer Efficiency on the Cooling Benefits of Green Roof
Irrigation. Environmental Research Letters, Volume 16(084062), pp. 1–13
Yildirim, S., Ozburak, C., Ozden, O., 2023. Green Roofs,
Vegetation Types, Impact on the Thermal Effectiveness: An Experimental Study in
Cyprus. Sustainability, Volume 15(2807), pp. 1–19