Published at : 29 Feb 2016
Volume : IJtech
Vol 7, No 2 (2016)
DOI : https://doi.org/10.14716/ijtech.v7i2.2981
Pangaribuan, A., Fadhil, Santoso, M.A., Dhiputra, I.M.K., Nugroho, Y.S., 2016. Controlling Fire Growth in Electrical Cable Compartment by Reducing Oxygen Concentration at Horizontal Orientation. International Journal of Technology. Volume 7(2), pp.332-342
Adrianus Pangaribuan | Fire Safety Engineering Research Group, Thermodynamics Laboratory Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok, Depok 16424, Indonesia |
Fadhil | Fire Safety Engineering Research Group, Thermodynamics Laboratory Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok, Depok 16424, Indonesia |
Muhammmad Agung Santoso | Fire Safety Engineering Research Group, Thermodynamics Laboratory Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok, Depok 16424, Indonesia |
I Made Kartika Dhiputra | Fire Safety Engineering Research Group, Thermodynamics Laboratory Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok, Depok 16424, Indonesia |
Yulianto Sulistyo Nugroho | Fire Safety Engineering Research Group, Thermodynamics Laboratory Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia, Kampus UI Depok, Depok 16424, Indonesia |
A series of laboratory tests for electrical fires have been carried out by researchers, and some of the results have confirmed and been adopted as standard. However, the studies focus on electrical fires in PVC insulation material and the melting temperature and toxicity of PVC insulation. By focusing on heat conductors, the growth and spread of a fire can be eliminated by reducing the oxygen concentration, especially inside the compartment. Electrical fires are the most common cause of compartment and building fires both internationally and nationally, according to statistics (Liu & Benichou, 2008). Whatever the triggers are inside the electrical compartment on the connection, termination, or cable, this research looks into electrical fires caused by 1.0–1.5 mmsq electrical cables. Electrical fires in cables are normally started by increasing temperatures inside the cable conductor. By controlling and adjusting the oxygen concentration inside the electrical compartment under atmospheric concentration, one can hamper a fire’s start, trigger, propagation, and growth. This study investigates the effectiveness of oxygen concentration on preventing the growth of fires triggered by electrical cabling. A series of studies were created in laboratory scale in a horizontal compartment with oxygen levels of 19%, 17%, and 15%. This paper presents the results of this experiment by studying the effects of reducing oxygen concentration on the fire growth in cable network in a horizontal orientation. The results show that controlling the oxygen concentration at levels lower than atmospheric concentrations can effectively reduce the propensity for cable ignition and lower the fire propagation rate.
Cable fire, Electrical fire, Electrical fire prevention, Oxygen controlling, Oxygen reduction
Anderson, P., Van Hess, P., 2000. Performance of Cables Subject to Thermal Radiation (SPReport 2000:24), Swedish National Testing and Research Institute, Boras
Babrauskas, V., 2003. Fires due to Electric Arcing: Can ‘Cause’ Beads be Distinguished from ‘Victim’ Beads by Physical or Chemical Testing?. Fire and Materials, pp. 189-201
Barnes, M.A., Briggs, P.J., Hirscler, M.M., Matheson, A.F. O'Neill, T.J., 1996. A Comparative Study of the Fire Performance of Halogenated and Non-Halogeneted Materials for Cable Aplications. Part I, Test on Materials and Insulated Wires. Fire and Materials, Volume 20, pp. 1-16
Bertrand, R., Chaussard, M., Gonzalez, R., Lacoue, J., Mattei, J.-M., Such, J.-M., 2001. Behavior of French of Cables under Fire Condition. In: Fire Science and Technology - Proceedings 5th Asia OceniaSymp. Univ. Newcastle, Autralia
Brabauskas, Vynthenis, 2003. Ignition Handbook. Published by Fire Science Publishers, Issaquah WA, USA. Co-published by the Society of Fire Protection Engineers. ISBN-10: 0-9728111-3-3; ISBN-13: 978-0-9728111-3-2
FEMA Installation, 2015. Residential Building Fires (2011–2013). Topical Fire Report Series, Volume 16, pp. 1-15
Hagimoto, Y., Watanabe, N., Okamoto, K., Watanabe, N., 2003. Short Circuit Fault in Electrical Cables and Cords Exposed to Radiant Heat. Fire and Materials. Interscience Communication Ltd., London
Hasegawa, H.K., Staggs, K., Fernandez-Pello, A.C., 1986. Procedure for Ranking Fire Performance of Electrical Cables (UCRL-93936). Lawrence Livermore National Laboratory, Livermore CA
Hasegawa, H.K., Alvares, N.J., Lipska-Quinn, A.E., Beason, D.G., Priante, S.J., Foote, K.L., 1986. Fire Protection Research for DOE Facilitties: FY 84-Year End Report (UCRL-53179-84), Lawrence Livermore National Laboratory, Livermore CA
Hoffman, J.M., Hoffman, D.J., Kroll, E.C., Wallace, J.W., Krool, M.J., 2003. Electrical Power Cord Damage from Radiant Heat and Fire Exposure. Fire Technology, pp. 21-48
McGrattan, K., Lock, A., Marsh, N., Nyden. M., Price, M., Morgan, A.B., Galaska, M., Schenck, K., 2010. Cable Heat Release, Ignition, and Spread in Tray Installations during Fire (CHRISTIFIRE). Office of Nuclear Regulatory Research, United States Nuclear Regulatory Commissions
Meyer, L.E., Taylor, A.M., York, J.A., 1990. Electrical Insulation Fire Characteristic. Flammability Tests, Volume 1
Nakagawa, Y.A, 1998. Comparative Study of Bench-scale Flammability Properties of Electric Cables with Different Covering Materials. Journal of Fire Sciences, Volume 16, pp. 179-205
Pangaribuan, A., 2007. Pengaruh Jenis Sambungan Kabel Listrik Terhadap Potensi Bahaya Kebakaran. MT Thesis, University of Indonesia
Liu, Z.G., Crampton, G., Kashef, A., Lougheed, G., Gibbs, E., Benichou, J.Z., Su, N., 2008. Fire Detectors, Fire Scenarios and Test Protocols. The Fire Protection Research Foundation, Canada